Application: | High-performance Transducer, Three Phase Transducer, General Transducer, High Frequency Converter Transducer |
---|---|
Output Type: | Triple |
Principle of Work: | Vector Control Transducer |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Supply voltage
|
380~480Vac(-15%~+10%)
|
Allowable
voltage unbalance
|
< 3%
|
Power supply
frequency
|
50/60Hz ±5%
|
Displacement power
factor
|
> 0.98
|
Harmonic interference Comply with EN61800-3 and EN12015
|
|
Output voltage
|
0-100% supply voltage
|
Output frequency
|
0-600Hz
|
Overload
performance
|
Light load application 110%, 1min; heavy
load application 150%, 1min; allowable overload frequency 1mim/10min
|
Maximum efficiency
|
≥96%~99%
|
Control mode
|
High-performance scalar, open-loop vector, closed-loop vector
|
Starting torque
|
150%, 3Hz; 150%, 3Hz; 200%, 0Hz
|
Carrier frequency
|
1.5-16kHz, carrier can be automatically adjusted
according to the load
|
AVR technology
|
Automatic regulation under bus voltage fluctuation
to stabilize output voltage
|
Frequency resolution
|
0.01Hz
|
Operation mode
|
Speed mode, torque mode, position mode
|
Command channel
|
Panel, control terminal, communication
|
Speed channel
|
Panel, digital quantity, analog quantity, communication,
pulse, internal calculation
|
Programmable digital input
|
7 channels, maximum load current 100mA
|
High-speed pulse
input signal
|
1 channel, 0-33kHz
|
Analog input
|
2 channels, 0-10V or 0 (4) -20mA
|
Programmable
digital output
|
2 channels, maximum drive capacity 20mA
|